Venetian blind actuator‚ 8x AC 230 V‚ 6A‚ with sunlight tracking of slats N 523/11

2015年4月22日 at 上午11:54分类:SIEMENS instabus

8 channels
V For the separate control per actuator channel of a sun protection‚ damper‚ door or window drive with
a motor for AC 230 V and electromechanical limit switches
V Rated contact voltage AC 230 V‚ 50 Hz
V Configurable behavior in the event of a bus voltage failure
V Configurable behavior in the event of a system voltage recovery
V Automatic mode for sunlight tracking control
V Manual mode
V Indication of direct operation with status object
V Status position of slats‚ 8-bit
V Integrated 1-/8-bit-scene control‚ 8 Scenes to be integrated per channel
V Suitable for integration in a sunlight tracking control system
V Sun protection control (up/down) using position data (8-bit value)
V Integrated power supply unit for the electronics‚ connected to AC 230 V
V Slat control (open/close) using position data (8-bit value) or travel to end position‚ stopping‚ stepwise
adjustment

Venetian blind actuator‚ 4 x AC 230 V‚ 6 A‚ with sunlight tracking of slats N 523/04

2015年4月22日 at 上午11:53分类:SIEMENS instabus

V 4 channels
V For the separate control per actuator channel of a sun protection‚ damper‚ door or window drive with
a motor for AC 230 V and electromechanical limit switches
V Rated contact voltage AC 230 V‚ 50 Hz
V Automatic mode for sunlight tracking control
V Manual mode
V Indication of direct operation with status object
V Status position of slats‚ 8-bit
V Suitable for integration in a sunlight tracking control system
V Sun protection control (up/down) using position data (8-bit value)
V Integrated power supply unit for the electronics‚ connected to AC 230 V
V Slat control (open/close) using position data (8-bit value) or travel to end position‚ stopping‚ stepwise
adjustment

Roller shutter actuator‚ 4 x AC 230 V‚ 6 A N 523/03

2015年4月22日 at 上午11:52分类:SIEMENS instabus

V 4 channels (one up and one down each)
V Rated contact voltage AC 230 V‚ 50 Hz
V Integrated 1-bit scene control‚ 2 Scenes to be integrated per channel
V Integrated power supply unit for the electronics‚ connected to AC 230 V
V Separate raising/lowering protection

Venetian blind actuator‚ 4 x AC 230 V‚ 6 A N 523/02

2015年4月22日 at 上午11:51分类:SIEMENS instabus

V 4 channels
V For the separate control per actuator channel of a sun protection‚ damper‚ door or window drive with
a motor for AC 230 V and electromechanical limit switches
V Rated contact voltage AC 230 V‚ 50 Hz
V Status position of slats‚ 8-bit
V Integrated 1-bit scene control‚ 2 Scenes to be integrated per channel
V Separate raising/lowering protection
V Integrated power supply unit for the electronics‚ connected to AC 230 V
V Sun protection control (up/down) using position data (8-bit value)

Venetian blind actuator‚ 4 x AC 230 V‚ 8 A‚ with limit position detection and sunlight tracking N 522/03

2015年4月22日 at 上午11:49分类:SIEMENS instabus

For the separate control per actuator channel of a sun protection‚ damper‚ door or window drive with
a motor for AC 230 V and electromechanical or electronic limit switches
V Integrated electronics for detection of the actuation of an electromechanical limit switch and with
auto-calibration of the travel time from one limit switch to the other
V Electrically interlocked relays to reverse the direction of rotation
V Relay contacts rated for nominal voltage AC 230 V‚ 8 A (resistive load)
V Configuration by the user whether all actuator channels are to be identically or individually parameterized
V Communication objects per actuator channel for moving the sun protection to the limit positions or
to stop travel and for step-by-step adjustment of the blind slats
V Communication objects for moving the sun protection and adjusting the blind slats directly to a new
position (as precisely as drive mechanics permit) by positioning commands as percentage values
V Automatic opening of blind slats up to a set position after the blinds have been lowered without any
stop from the upper to the lower limit position
V Integrated 1-bit scene control for save and recall of 2 favored positions of blind and slats
V Integrated 8-bit scene control and assignment of up to 8 scenes per channel
V Optional object “Sunshine” for activation / deactivation of sunlight tracking of the slats for shading
with greatest possible daylight component
V Differentiation between automatic and manual mode and with automatic switchover from automatic
to manual mode of the respective actuator channel on activation of a bus pushbutton for manual control
of the sun blind
V Priority of manual mode over automatic positioning commands
V Alarm object per device or per channel for moving the sun protection to the configured safety position
in the event of a wind alarm e.g. and with blocking of travel to another position as long as alarm pending
V Travel blocking object per device or per channel for blocking the sun protection in its current position
(needed during cleaning of an outdoor Venetian blind e.g.)
V Status objects per actuator channel for query or automatic transmission of sun blind and slat position
as percentage value
V Electronics powered via an integrated power supply unit for AC 230 V
V Green LED for displaying the 230 V operating voltage
V Pushbutton for switchover between bus mode and direct mode
V Yellow LED for display of activated direct mode
V Two pushbuttons each per actuator channel for drive control in direct mode
V Integrated in the actuator housing and operational if the actuator is supplied with AC 230 V (even if
bus voltage missing or communication not operational)
V Integrated bus coupling unit with only half a standard bus load
V Bus connection via bus terminal or contact system to data rail
V Modular installation devices for mounting on TH35 EN 60715 mounting rail

Presence detectors

2015年4月22日 at 上午11:48分类:SIEMENS instabus

V Used as passive infrared detector for indoor ceiling installation
V Sensing range‚ horizontal 360 °‚ vertical approx. 100°‚ rotating/swiveling sensor head‚ optionally for
shading off parts of the sensing range
V For monitoring an area for presence up to approx. 6 x 3.5 m‚ for a mounting height of 2.8 m (presence
detection)‚ motion detection up to 5 x 3.5 m
V Mixed light measurement‚ measuring range 20…1000 lux
V Presence detection for three function blocks (presence detector‚ motion detector and HVAC detector)
V Functions: Switching on/off‚ 8-bit value‚ 16-bit value‚ temperature value‚ brightness value‚ 8-bit scene
control
V Blocking object per function module
V Adjustable delay time per function module‚ which can be optionally set to a fixed time‚ or two times
that can be switched between via bus‚ or set to one value via bus
V Parallel operation of several presence detectors (master-slave‚ master-master) without logic modules
V Integrated IR receiver for S 255/11 IR remote control with six pushbutton pairs (see accessories)
V In the case of individual pushbuttons‚ selectable function per pushbutton: Switching Over‚ Switching
On‚ Switching Off‚ call up 8-bit scene‚ 8-bit value‚ 16-bit value‚ temperature value‚ brightness value
V In the case of pushbutton pairs‚ selectable function Switching on/off‚ switching over/over‚ 2-pushbutton
dimming with stop telegram‚ 2-pushbutton sun protection control‚ transmit variable 8-bit value‚
8-bit scene control
V Blocking object for IR receiver decoder
V LED for display of detected motions in test mode
V Mounting on the ceiling in a flush-mounting device box with 60 mm diameter and at least 40 mm
mounting depth‚ or in an AP 258E surface-mounting enclosure‚ which must be ordered separately (see
accessories)

Presence detector with brightness sensor UP 258E21
V Integrated constant light level control and 2-step light control‚ optionally available in fully automatic
or semi-automatic version
V 4 channels for offset groups

 

Motion detector with brightness sensor UP 258D11
V Integrated 2-step light control‚ optionally available in fully automatic or semi-automatic version
V 3 independent control channels each with 2 start objects and 2 end objects

Switch / dimming actuator‚ triple‚ 230 V AC‚ 50 / 60Hz‚ 6A‚ with integrated constant light level control N 526/02

2015年4月22日 at 上午11:47分类:SIEMENS instabus

Can be operated per channel as a pure switching/dimming actuator or as a constant light controller in
master or slave operation mode
V 3 switch outputs for the connection of max. 30 electronic ballasts for 2 x 36 W FL/max. 20 electronic
ballasts for 1 x 58 W FL or max. 15 electronic ballasts for 2 x 36 W FL/max. 10 electronic ballasts for 2
x 58 W FL
V 3 control voltage outputs DC 1-10 V for the connection of max. 50 dimmable electronic ballasts
V 3 inputs for the connection of one brightness sensor GE 255/x each via a 3-core‚ max. 100 m long
cable‚ which is also used as a power supply for the sensor electronics
V Communication objects for sending the measured brightness values
V Communication objects per actuator channel to control the following operating modes: comfort
mode‚ automatic mode and night operation as well as switching‚ dimming and value setting
V Time-dependent activation of the lighting during night operation (lighting for cleaners)
V Automatic toggling from automatic to manual operation of the relevant actuator channel when the
bus push button is pressed for manual switching and dimming of this channel (constant light control
inactive during manual operation)
V Status objects per channel for switching state or dimming value
V Integrated power supply unit for AC 230 V‚ 50 Hz to supply the actuator electronics and a green LED
for operational display
V Push button per actuator channel for local switching of the outputs or for starting a calibration of the
sensor‚ integrated in the actuator housing and able to function even when the bus cable is not
installed and when there is a failure of the bus communication
V Connection of the 230 V supply voltage and all the outputs/inputs via screw terminals 0.5 … 4 mm
V Integrated bus coupling unit‚ bus connection via bus terminal
V Modular installation devices for mounting on TH35 EN 60715 mounting rail

Switch/dimming actuator 8 x AC 230 V‚ 16 A‚ 1…10 V‚ UL standard N 526E02

2015年4月22日 at 上午11:46分类:SIEMENS instabus

For switching and dimming of eight mutually independent groups (channels) of fluorescent lamps
with dimmable electronic control gear (ECG)
V 8 control voltage outputs 1…10 V DC
V Control power min. 60 OSRAM ECG dynamic each
V 8 switching outputs (relay contacts) for 230 V AC‚ 50/60 Hz‚ 16 A at p.f. = 1
V Each of them for connection of min. 30 OSRAM ECG dynamic for 58 W fluorescent lamps
V Slide switch per relay output for manual operation and switch position indication
V Selection between identical or individual configuration of all channels
V Command objects for each actuator channel for switching on/off‚ dimming brighter/darker and
set/value
V One 1-bit and one 8-bit-status object (switching state and dimming value) per output
V Per channel configurable time-limited activation of the lighting during night mode (base lighting)
V Warning 30 seconds prior to imminent switch off by dimming to 50 % of the previous dimming value
for each channel with time-limited operation
V Switching on or off of a channel by dimming brighter/darker
V Configurable dimming value upon switching on
V Jumping or dimming to a new dimming value
V Configurable dimming time from 0…100%
V Integrated 8 bit scene control and assignment of each output to up to 8 scenes
V Transmission of status objects on request‚ cyclically and/or automatically after changes
V Configurable behaviour on bus voltage failure and recovery
V Bus-powered electronics
V Integrated bus coupling unit‚ bus connection via bus terminal or contact system to data rail
V Modular installation devices for mounting on TH35 EN 60715 mounting rail

Switch/dimming actuator‚ 8 x DALI‚ 8 ECGs per DALI output N 525E01

2015年4月22日 at 上午11:45分类:SIEMENS instabus

8 DALI outputs
V Control capacity for up to 8 DALI-ECGs per DALI output
V Power supplied to the electronics and the DALI outputs through an integrated power supply unit for
230 V AC
V Green LED for status display
V Pushbutton for selecting and switching over 4 DALI outputs respectively between bus and direct mode
V Yellow LED for indicating which 4 DALI outputs the direct mode is activated for
V 1 red LED per DALI output for indicating the circuit state or fault (e.g. lighting medium failure) of the
connected group
V Four pushbutton pairs for switching and dimming of 4 DALI outputs in direct mode‚ functional when
230 V AC is applied (also when no bus voltage is connected and also when bus communication has
not yet been started or is interrupted)
V Selection of identical or individual configuration of all DALI outputs
V Selectable operating mode per DALI output (normal mode‚ 1-level or 2-level time-switch mode)
V Per DALI output with command objects for switching on/off‚ dimming brighter/darker and setting dimming
value
V Per DALI output optionally with up to 4 add-on status objects (circuit state and lighting medium failure‚
dimming value status and DALI status)
V Sending of status objects on request and/or automatically after change
V Per DALI output with add-on object for time-limited switching on of lighting in night mode (cleaning
light)
V Warning approx. 1 minute before imminent switching off‚ by dimming to 50 % of former dimming value
in night or timer mode
V Adjustable switching on and/or off of a channel through dimming brighter/darker‚ dimming value
when switching on‚ actuating or dimming a new dimming value‚ dimming time from 0% to 100%
V Adjustable behavior on bus voltage or mains voltage failure and bus voltage or mains voltage recovery
V Add-on object and integrated 8bit scene control for saving and restoring up to 16 scenes per DALI output
V Integrated bus coupling unit as only half standard bus load
V Bus connection through bus terminal as well as contact system to data rail
V Device for mounting on rail TH35 DIN EN 60715

KNX / DALI Gateway Twin N 141/31

2015年4月22日 at 上午11:44分类:SIEMENS instabus

V Communication via KNX EIB with electronic ballasts (ECG) with a DALI interface
V Two (2) DALI output acc. to IEC 60929‚ each for communication with up to 64 DALI ballasts and at
least 10 sensors
V Integrated power supply with input voltage 110…240 V AC‚ 50…60 Hz or 120…240 V DC for powering
the gateway electronics and DALI output
V Maximum DALI output voltage of 19 V‚ short circuit resistant
V Incorrect voltage detection during commissioning‚ whether incorrect power line is connected to a
DALI output
V LC display for displaying operation mode and error messages
V Pushbutton for switching between bus and direct operating mode
V One pair of push buttons for switching On/Off of all connected DALI ballasts
V One LED per DALI output for status signal of all connected luminaries in direct mode
V Configurable assignment of max. 128 DALI ECG to max. 32 DALI groups‚ exclusive controlled in groups
(switching‚ dimming‚ set dimming value) and feedback for group status and lamp failure
V Configurable behaviour for bus failure (stand-alone mode)
V Control (switching‚ dimming‚ set dimming value) of all connected luminaries together in broad-cast
mode
V Status signal and display of lamp and ECG failure per group and per DALI device
V Possibility to reintegrate defective DALI ECG without software
V One or two level timer
V Integrated scene control for up to 32 scenes
V 16 integrated 2-level-controller for brightness control
V Assignment of DALI ECG to groups and test option for ECG‚ groups and scenes via ETS during commissioning
V Assignment of DALI sensors and test option of sensors via ETS during commissioning
V Integrated bus coupling unit with only half a standard bus load‚ bus connection via bus terminal
V Mounting on DIN rail EN 60715-TH35-7.5